Liquid Cooling System
• Circulating liquid cooling, low noise, low loss
Advanced Fire Protection Design
• Three-level fire protection, with built-in fire detectors, aerosol modules, sound and light fire alarms, EMS modules + Gateways, and immersion sensors
Highly Flexible Design
• Supports parallel operation of 2-10 units, with reserved MPPT expandable space
Application scenarios
• Intelligent peakshaving and valleyfilling, efficient photovoltaic energy utilization, and flexible transformer expansion, Back-up(Manual Switch)
Three-Phase topology
• Three-phase four-branch inverter, with a three-phase imbalance coefficient of 0% and a power factor (PF) of 1
Safetyand Durability Appearance
• Outdoor cabinet anti-corrosion, flame-retardant design, battery compartment IP65, electrical compartment IP55
Intelligent Platform Operation and Maintenance
• SaaS all-day remote monitoring platform with data independence, real-time tariff collection, AI intelligent scheduling, time scheduling can be completed within 0.2s
| System Description | |
| Rated Power | 125kW |
| Battery Capacity | 261kWh |
| DC Parameters | |
| Battery Type | LFP/314Ah |
| PACK Specification | 1P52S/52kWh |
| Rated Voltage | 832V |
| Voltage Range | 728-949V |
| Charge/Discharge Rate | ≤0.5C |
| Depth of Discharge (DoD) | 0.98 |
| AC Parameters (Grid-tied) | |
| Rated Power | 125kW |
| Rated Voltage | 400V |
| Rated Frequency | 50Hz |
| Power Factor | -1...+1 |
| Connection Method | Three-phase four-wire |
| System Parameters | |
| Dimensions (WHD) | 1000*2500*1450mm |
| Weight | 2500kg |
| Protection Rating | IP55 |
| Cable Entry | Bottom/Bottom or Side/Side |
| Cooling Method | Liquid Cooling |
| Fire Protection | Standard: Aerosol/Optional: Perfluorohexanone + Water Fire Suppression |
| Enclosure Corrosion Protection | C3/C5(Optional) |
| Operating Environment | -25~60℃ |
| Altitude | 3000m |
| Noise Level | 85dB |
| Communication Interface | Ethernet /CAN/RS-485 |
| Communication Protocol | TCP/CAN2.0/Modbus |